MEDIUM VOLTAGE · 19 / 33 kV · IEC 60502-2

كابل XLPE 33 kV

Primary distribution in dense urban networks, substation feeders and large wind farm collection. Three-core or single-core construction, copper or aluminium conductor, manufactured against IEC 60502-2 with project-specific screen sizing, armour and sheath.

Cu / Al الفئة 23-core & single coreSTA · SWA · AWA25–630 mm²PD ≤ 10 pC
النوعCU/XLPE/CWS/STA/PVC
U₀/U (Uₘ)19 / 33 kV (36 kV)
العزلXLPE, 8.0 mm nominal
Metallic screenCu wire screen per IEC 60502-2
الدرعSTA (SWA / AWA optional)
الغمدPVC ST2 black (PE / LSZH optional)
Routine voltage testAC 66.5 kV / 5 min
Partial discharge≤ 10 pC at 32.9 kV (1.73 U₀)
Impulse (type test)170 kV
Medium voltage aluminium cable - Lulian Cable product view
Medium voltage aluminium cable

§01 — Cable construction

The reference construction, layer by layer.

At 19/33 kV (Uₘ 36 kV) the 8.0 mm insulation wall and the heavy bedding/armour package make this the largest three-core build in the MV range. Joint bay planning, drum lengths and pulling tensions are agreed before production, because every avoidable joint on a 33 kV route is a cost — both at installation and over the cable life.

Technical data — reference only. Figures in the tables below are reference values for early-stage project comparison. Conductor size, insulation and sheath thickness, overall diameter, DC resistance and ampacity are confirmed against the approved cable schedule and the applicable standard (IEC 60502-2 / GB/T 12706) before production. Ampacity is quoted for installation in free air at 40 °C ambient; ratings for buried, in-conduit or tray installation differ. Dimensional and electrical tolerances follow the relevant standard.
#الطبقةReference detail
01الموصلCu class 2 stranded (RM). Sector-shaped (SM) for 3-core ≥ 185 mm².
02Conductor screenExtruded semiconducting compound, ≤ 0.5 mm nominal thickness.
03عزل XLPEExtruded XLPE, 8.0 mm nominal at the 36 kV class (IEC 18/30 table; BS 6622 19/33 practice).
04Insulation screenExtruded semiconducting, strippable or bonded per requirement.
05Metallic screenCu wire screen, 16–35 mm² by conductor size; for long 33 kV feeders the screen is verified against the full single-phase earth-fault duration.
06Inner sheathPVC ST2, extruded bedding.
07الدرعDouble steel tape (STA) for direct burial; SWA for higher tensile load; AWA for single-core.
08ServingAnti-corrosion wrap on certain designs (optional).
09Outer sheathPVC ST2 black; PE or LSZH on request.
Single-core 33kV class medium voltage cable with copper conductor, metallic screen and wire armour
33kV single-core armoured construction

§02 — Technical specifications

Electrical parameters — 19 / 33 kV class.

Conductor (mm² Cu)Insulation thicknessDC resistance @20 °C (Ω/km)Indicative current, direct burial 25 °C (A)
3 × 358.0 mm0.524~170
3 × 508.0 mm0.387~205
3 × 708.0 mm0.268~250
3 × 958.0 mm0.193~300
3 × 1208.0 mm0.153~345
3 × 1508.0 mm0.124~385
3 × 1858.0 mm0.0991~435
3 × 2408.0 mm0.0754~500
3 × 3008.0 mm0.0601~560
3 × 4008.0 mm0.0470~640

DC resistance values per IEC 60228. Indicative current: ground 25 °C, soil thermal resistivity 1.5 K·m/W, depth 1.0 m, flat formation — reference only; final ampacity is calculated against your installation conditions. Overall diameter and weight for this voltage class are issued in the project datasheet with the formal offer.

§02B — Worked example · 19 / 33 kV

Conductor selection by short-circuit duty on a 33 kV primary feeder.

For a prospective fault of 25 kA with 1 s clearing: S ≥ I · √t / k = 25 000 / 143 ≈ 175 mm², so 185 mm² is the minimum Cu cross-section — independent of the load current. On real 33 kV routes the short-circuit figure, not ampacity, usually decides the conductor. Send the network fault data and we run both checks and state them in the datasheet.

§03 — Standards

Standards printed on the sheath and on the drum card.

IEC 60502-2GB/T 12706.2BS 6622BS 7835 (LSZH)IEC 60332-3CIEC 61034-2IEC 60754-1/2EN 50575 CPRICEA S-10634

§05 — Quality testing

What we test on every drum.

Routine tests run on every drum; sample tests on each batch; type tests on new constructions witnessed by CNAS-accredited third-party labs.

  • Conductor DC resistance at 20 °C (routine)
  • AC voltage withstand AC 66.5 kV / 5 min (routine)
  • Partial discharge ≤ 10 pC at 32.9 kV (1.73 U₀) (sample)
  • Insulation thickness & eccentricity (sample)
  • Metallic screen cross-section (routine)
  • Armour coverage & bedding integrity (routine)
  • Sheath thickness + spark test (routine)
  • Bending test + voltage after bending (type)
  • Impulse voltage 170 kV (type)
Routine electrical testing of medium voltage cable in the Lulian in-house laboratory
Routine electrical test · in-house lab

§06 — Packaging & delivery

Drums sized for the cable, not for the workshop.

33 kV drums carry the routine test report on the drum card — including the 66.5 kV / 5 min withstand record — together with drum length and serial marking for joint-bay planning. Wooden drums with fumigation marks for export; steel-plywood drums for heavy cross-sections. Cable ends sealed with heat-shrink caps; shipping marks per the buyer’s format.

Standard drum lengths: 500 / 1000 / 1500 / 2000 m. Lead time: 25–35 working days for stocked constructions; 40–55 working days for project-specific builds.

§07 — FAQ

Common questions on 33 kV cable procurement.

What is the U₀/U rating of 33 kV XLPE cable?

19 / 33 kV, Uₘ = 36 kV per BS 6622 — the top of the MV range, equivalent to the IEC 18/30 (36 kV) class. For 35 kV systems we supply the 26/35 kV construction under GB/T 12706.3.

What conductor cross-sections are available?

Three-core: 25–400 mm². Single-core: 25–630 mm². Copper or aluminium, class 2 stranded; sector-shaped conductors for large 3-core sizes.

Can the cable be direct-buried?

Yes. The armoured construction (STA) with PVC ST2 outer sheath is rated for direct burial. SWA is recommended where tensile load or rodent risk is high.

What is the partial discharge limit?

≤ 10 pC measured at 32.9 kV (1.73 U₀) per IEC 60502-2. PD is measured on every drum and documented on the routine test report.

What routine and type tests are performed?

Routine on every drum: conductor DC resistance, AC voltage withstand AC 66.5 kV / 5 min, sheath spark test. Sample: PD, insulation thickness, screen check. Type: bending + voltage, load cycle, impulse voltage 170 kV.

Can the cable be supplied with LSZH sheath?

Yes, for tunnel, metro, data centre and indoor substation use. Verified against IEC 61034 (smoke density) and IEC 60754 (acid gas).

How are joint bays planned on a long 33 kV route?

Drum length decides the joint spacing, so we agree drum lengths against the route profile before production — typical lengths are 500–1 000 m on this class. Each drum is numbered against the joint-bay schedule and the pulling tension per section is stated in the installation notes.

أرسل جدول الكابلات. نؤكد التركيب خلال 24 ساعة.

Share voltage class, conductor material & size, core count, armour, sheath, installation method, total length and drum preference.

طلب عرض السعر بالبريد → sales@luliancable.comافتح نموذج RFQ

الجهد (U₀/U)19 / 33 kV
الموصلCu / Al الفئة 2
Cross-section3 × 185 mm² (typical)
الدرعSTA / SWA / AWA
الغمدPVC ST2 · black
المعيارIEC 60502-2
إنكوتيرمFOB تشينغداو · CIF [منفذ]