CONTROL CABLE · LSZH · GB/T 9330-2020 · TYPE TEST 202521001018

LSZH Control Cable — with the test report, not just the claim.

Low smoke zero halogen flame-retardant control cable for tunnels, metros, data centres and public buildings. Our WDZC-KYJY passed a complete third-party type test against GB/T 9330-2020 — smoke transmittance 80 % against a 60 % requirement, bunched flame class C, halogen-free. The measured values are published below.

450/750 V2–61 cores0.75–10 mm²IEC 60332-3CSmoke 80 % (req ≥60 %)

§01 — Third-party type test evidence

Third-party verified. Our LSZH control cable is verified by independent test report No. 202521001018 — WDZC-KYJY 450/750 V, 37 × 1.5 mm², to GB/T 9330-2020; smoke transmittance 80% (low-corrosive, flame-retardant). Full measured values are shown below.

Report No. 202521001018 — measured values, not marketing words.

Type test of WDZC-KYJY 450/750 V 37×1.5 by Qingdao Product Quality Testing Research Institute / National Electronics and Electric Appliance Safety Quality Inspection and Testing Center (CNAS L1184), against GB/T 9330-2020. Conclusion: conforms.

Electrical & construction results

Technical data — reference only. Figures in the tables below are reference values for early-stage project comparison. Conductor size, insulation and sheath thickness, overall diameter, DC resistance and ampacity are confirmed against the approved cable schedule and the applicable standard (GB/T 9330 / IEC 60245) before production. Ampacity is quoted for installation in free air at 40 °C ambient; ratings for buried, in-conduit or tray installation differ. Dimensional and electrical tolerances follow the relevant standard.
Test itemRequirementMeasured
Conductor DC resistance at 20 °C≤ 12.1 Ω/km11.5 Ω/km
Finished cable voltage test (3000 V / 5 min)No breakdownNo breakdown
Core voltage test (2000 V / 5 min)No breakdownNo breakdown
Insulation resistance at 90 °C≥ 1.10 MΩ·km1090–2535 MΩ·km
Insulation thickness (average / minimum)≥ 0.6 / ≥ 0.44 mm0.7 / 0.64 mm
Sheath thickness (minimum)≥ 1.35 mm1.93 mm
Average overall diameter≤ 26.2 mm25.9 mm

Fire performance results

Test itemRequirementMeasured
Bunched flame test, class C (char height)≤ 2.5 m0.6 m
Single-core vertical flame testChar limits per IEC 60332-1Passed, no dripping ignition
Smoke density (minimum light transmittance)≥ 60 %80 %
pH of evolved gases (insulation / tape / sheath)≥ 4.35.3 / 5.0 / 5.1
Conductivity of evolved gases≤ 10 μS/mm1 μS/mm
Acid gas content≤ 0.5 %< 0.5 %
Fluorine content≤ 0.1 %Not detected (limit 0.02 %)
Type test report cover No. 202521001018 for WDZC-KYJY LSZH control cable, Qingdao testing institute
Report cover · No. 202521001018 · CNAS L1184
Test report results page showing measured conductor resistance and voltage test values
Electrical results page (excerpt)
Test report fire performance page showing bunched flame class C, smoke density 80 percent, pH and conductivity results
Fire performance results page (excerpt)

Full report issued with the formal offer and available in the shipping document package. Values above are transcribed from report No. 202521001018 without alteration.

§02 — Product range

The WDZ family — built on the same compounds.

WDZC-KYJY

LSZH control cable, class C

XLPE insulation, polyolefin sheath, 450/750 V. The tested construction shown on this page. Screened variants WDZC-KYJYP / KYJYP2 for EMI-sensitive loops.

WDZ-YJY

LSZH power cable 0.6/1 kV

Low-smoke halogen-free power distribution for buildings and tunnels; single and multi-core, armoured options.

WDZN-YJY

LSZH fire-resistant cable

Adds fire-resistance (circuit integrity during fire, IEC 60331) on top of LSZH and flame-retardant ratings, for life-safety circuits.

§03 — Standards

Verified against these standards.

GB/T 9330-2020IEC 60332-3CIEC 60332-1IEC 61034-1/2 (smoke)IEC 60754-1/2 (halogen)IEC 60331 (fire-resistant variants)GB/T 19666

§04 — Applications

Where LSZH is not optional.

METRO & TUNNEL

Metro station and tunnel control circuits

Emergency lighting, ventilation and fire-alarm control loops where smoke and halogen limits are mandatory.

DATA CENTRE

Data centre control cabling

BMS and environmental monitoring control circuits in white space where corrosive gas is unacceptable.

HOSPITAL & PUBLIC

Hospitals and public buildings

Life-safety control wiring in occupied buildings — low smoke protects escape routes.

AIRPORT & RAIL

Airport and railway control panels

Signalling and interlocking control cables with low-smoke halogen-free requirements.

§05 — FAQ

Common questions on LSZH control cable.

What does LSZH mean, and how is it different from flame-retardant and fire-resistant?

They are three different properties. LSZH (Low Smoke Zero Halogen) describes what the cable emits when it burns: little smoke and no halogen acid gas (verified by IEC 61034 and IEC 60754). Flame-retardant (ZR) describes how well the cable resists flame propagation (IEC 60332). Fire-resistant (NH) describes whether the cable keeps working during a fire (IEC 60331). A cable can carry one, two or all three ratings — our WDZC-KYJY is LSZH + flame-retardant class C.

Which standard does the WDZC-KYJY control cable comply with?

GB/T 9330-2020 for the control cable itself, plus IEC 60332-3 class C for bunched flame performance, IEC 61034 for smoke density, and IEC 60754 for halogen acid gas. The complete type test was performed by Qingdao Product Quality Testing Research Institute (CNAS L1184) — report No. 202521001018.

What sizes and core counts are available?

450/750 V control cables from 2 to 61 cores, 0.75–10 mm², copper class 1 or class 5 conductors, with or without copper-tape or braided screen (WDZC-KYJY / WDZC-KYJYP / WDZC-KYJYP2). Confirm the core count and screen requirement with your RFQ.

Can you issue the type test report to our inspector?

Yes. The full report No. 202521001018 is shared with the formal offer and included in the shipping document package on request. Third-party witnessed tests (SGS / BV / Intertek) are available for project orders.

Is LSZH more expensive than PVC, and when is it mandatory?

LSZH compounds cost more than PVC, typically adding 10–20 % to the cable price. It is mandatory in most tunnel, metro, data centre, hospital and marine specifications, and wherever IEC 60364 or the local fire code limits smoke and corrosive gas in occupied escape routes.

Send the core schedule. We confirm construction in 24 hours.

Share: core count & cross-section, screen requirement, voltage rating, flame class, total length and destination port. The type test report comes with the offer.

طلب عرض السعر بالبريد → sales@luliancable.comافتح نموذج RFQ

النوعWDZC-KYJY 450/750 V
Cores × sizee.g. 37 × 1.5 mm²
ScreenNone / Cu tape / braid
Flame classIEC 60332-3 C
Smoke / halogenIEC 61034 / 60754
المعيارGB/T 9330-2020
أدلةاختبار النوع 202521001018

§06 — Related

منتجات مجاورة وقراءة.

ورقة بيانات

Download the datasheet.

Construction, test values and reference dimensions as a PDF. We send it to your work email address — so the file reaches the engineer who needs it, and so we can answer the dimension questions that follow.

Get the LSZH control cable datasheet (PDF) by email

Tender pack or procurement portal? Send the enquiry and we add the datasheet and the type test documentation to your document set.

أرسل استفسارًا

اطلب عرض سعر

ثلاثة حقول. رد فني خلال 24 ساعة.