Solar & Renewable Energy Cable Solutions

Solar & Renewable Energy Cable Solutions

§01 — What the site demands

Conditions on wind farm and solar plant cable routes

Renewable sites are geographically large and electrically simple: many small sources collected at medium voltage and delivered to one or two grid connection points. Length, not current rating, becomes the governing constraint — on a turbine string or array feeder several kilometres long, voltage drop usually decides the cross-section. The environment adds UV, high ambient temperature, sand abrasion, coastal salt and repeated twisting of the run inside a turbine tower.

Site circuitCondition in serviceWhat it fixes in the cable
Wind farm collection20 kV, 33 kV or 35 kV strings to the collector substationMV XLPE build sized for load current and drop along the string
Turbine internal cablingVertical runs with torsional movementFlexible conductors, secure cleating, twist loops
Solar array DC feedersDC at maximum voltage including open-circuit voltage at the lowest temperatureInsulation rated for DC stress, UV- and heat-resistant sheath
Inverter output and auxiliaries0.6/1 kV AC, grouped in trenches or on racksDerating for grouping and ambient
Exposed and above-ground sectionsDirect sun, high ambient, sand or saltUV-stabilised sheath, temperature-corrected rating
SCADA and communicationsLong distances to the control buildingOptical fibre on the structures or in the trench

On long collection circuits the first calculation is voltage drop. Sizing on current alone gives cable that is thermally adequate and electrically unusable.

§02 — Recommended cable families

Families that match renewable duties, and why

33 / 35 KV

MV XLPE for collection networks

Collector circuits linking turbines or block substations to the grid connection point run at 20 kV, 33 kV or 35 kV: see 33 kV XLPE cable and the MV range.

0.6/1 KV

LV XLPE for inverter outputs

Inverter-to-transformer connections and balance-of-plant loads run at 0.6/1 kV under IEC 60502-1, corrected for ambient and grouping: see LV XLPE power cable.

LSZH

Low-smoke cable in enclosures

Inverter stations and control buildings call for low smoke and acid gas, measured by IEC 61034 and the IEC 60754 series: see LSZH control cable.

CONTROL

Control cable for monitoring

Pitch and yaw control, inverter signalling and metering travel beside power cable, so screened control cable keeps interference out of instrumentation: see KVV and KVVP control cable.

AERIAL FIBRE

Optical fibre for SCADA links

Turbine-to-substation communications and protection signalling run on fibre, unaffected by lightning and switching transients: see ADSS and OPGW aerial fibre.

ARMOURED

Armoured construction for trenched routes

Trenched collection circuits use steel-tape armoured cable, with a UV-resistant sheath at above-ground transitions: see YJV22 armoured power cable.

§03 — Selection checklist

Decisions that change cost and availability

DecisionWhat has to be settledConsequence if ignored
Voltage dropCross-section checked at the actual string length and loadAdequate rating but unusable voltage at the far end
Ambient deratingRating corrected to the site’s design maximum ambientCable above its rated conductor temperature in summer
GroupingNumber of circuits touching in trenches or on racksUnderestimated heating across the whole site
UV exposureUV-stabilised sheath on any unburied sectionSheath cracking and chalking within a few seasons
Conductor materialAluminium or copper, with matching lugs and jointing practiceTermination problems and corrosion at joints

Derating factors for ambient temperature and grouping come from the wiring rules the project adopts, typically IEC 60364-5-52 or its local equivalent. Name the document.

§04 — Questions from EPC and developer engineers

Frequently asked questions

Aluminium or copper for array and collector feeders?

Aluminium is lighter and usually cheaper per ampere on long runs, suiting trench-based collection circuits; copper is easier to terminate and tolerates repeated handling. Lugs, jointing compound and tooling must match the conductor, and bi-metallic transitions must be specified where the two meet.

How much derating is needed for a hot climate site?

It depends on the design maximum ambient temperature, the laying arrangement and the number of grouped circuits — there is no single figure. Provide the site’s temperature data and trench layout and ratings follow from the wiring rules.

Do above-ground sections need a different sheath?

Yes. Exposed runs need a sheath compound stabilised against ultraviolet radiation, identified by carbon-black content or a UV-resistance test, and the rating has to be corrected for solar gain in full sun.

Why is fibre preferred for site communications?

Routes are long and share the electromagnetic and lightning environment of the power circuits. Fibre is immune to induced voltage, needs no surge protection along the route, and carries SCADA, protection signalling and video on one cable.

§05 — Next step

From site layout to a quotation

A workable enquiry carries the collection voltage, the string or array layout with lengths, load per circuit, temperature and UV conditions, and the installation method per section. Drum lengths matter too, since long runs are supplied in drum multiples. A typical distribution project brief shows the input level that makes quotations comparable; our testing and certification page lists the documents supplied per shipment.

Send the layout and site conditions and we will return construction and drum planning: Request a quotation →