MEDIUM VOLTAGE · 6 / 10 kV · IEC 60502-2

Cable XLPE 10 kV

The export workhorse: utility MV distribution in Africa, SE Asia and Latin America where 10 kV nominal is standard. Three-core or single-core construction, copper or aluminium conductor, manufactured against IEC 60502-2 with project-specific screen sizing, armour and sheath.

Cu / Al clase 23-core & single coreSTA · SWA · AWA25–630 mm²PD ≤ 10 pC
TipoCU/XLPE/CWS/STA/PVC
U₀/U (Uₘ)6 / 10 kV (12 kV)
AislamientoXLPE, 3.4 mm nominal
Metallic screenCu wire screen per IEC 60502-2
ArmaduraSTA (SWA / AWA optional)
CubiertaPVC ST2 black (PE / LSZH optional)
Routine voltage testAC 21 kV / 5 min
Partial discharge≤ 10 pC at 10.4 kV (1.73 U₀)
Impulse (type test)95 kV
Three-core aluminium conductor MV cable - Lulian Cable product view
Three-core aluminium conductor MV cable

§01 — Cable construction

The reference construction, layer by layer.

The 6/10 kV class is the workhorse of public MV distribution: a 3.4 mm XLPE wall, screened cores, and a bedding/armour package chosen for the laying condition. Sector-shaped cores keep the three-core build compact above 185 mm². Screen cross-section is confirmed against the network earth-fault data before production; for rural feeders we also agree drum lengths so the number of joints stays low.

Technical data — reference only. Figures in the tables below are reference values for early-stage project comparison. Conductor size, insulation and sheath thickness, overall diameter, DC resistance and ampacity are confirmed against the approved cable schedule and the applicable standard (IEC 60502-2 / GB/T 12706) before production. Ampacity is quoted for installation in free air at 40 °C ambient; ratings for buried, in-conduit or tray installation differ. Dimensional and electrical tolerances follow the relevant standard.
#CapaReference detail
01ConductorCu class 2 stranded (RM). Sector-shaped (SM) for 3-core ≥ 185 mm².
02Conductor screenExtruded semiconducting compound, ≤ 0.5 mm nominal thickness.
03Aislamiento XLPEExtruded XLPE, 3.4 mm nominal across 16–1 000 mm² at 6/10 kV per IEC 60502-2, table 6.
04Insulation screenExtruded semiconducting, strippable or bonded per requirement.
05Metallic screenCu wire screen per IEC 60502-2; the minimum cross-section rises with conductor size — 16 mm² (≤ 120 mm²), 25 mm² (150–300 mm²), 35 mm² (400–630 mm²).
06Inner sheathPVC ST2, extruded bedding.
07ArmaduraDouble steel tape (STA) for direct burial; SWA for higher tensile load; AWA for single-core.
08ServingAnti-corrosion wrap on certain designs (optional).
09Outer sheathPVC ST2 black; PE or LSZH on request.
Single-core 10kV class medium voltage cable with copper conductor, metallic screen and wire armour
10kV single-core armoured construction

§02 — Technical specifications

Electrical parameters — 6 / 10 kV class.

Conductor (mm² Cu)Insulation thicknessDC resistance @20 °C (Ω/km)Indicative current, direct burial 25 °C (A)
3 × 353.4 mm0.524~170
3 × 503.4 mm0.387~205
3 × 703.4 mm0.268~250
3 × 953.4 mm0.193~300
3 × 1203.4 mm0.153~345
3 × 1503.4 mm0.124~385
3 × 1853.4 mm0.0991~435
3 × 2403.4 mm0.0754~500
3 × 3003.4 mm0.0601~560
3 × 4003.4 mm0.0470~640

DC resistance values per IEC 60228. Indicative current: ground 25 °C, soil thermal resistivity 1.5 K·m/W, depth 1.0 m, flat formation — reference only; final ampacity is calculated against your installation conditions. Overall diameter and weight for this voltage class are issued in the project datasheet with the formal offer.

§02B — Worked example · 6 / 10 kV

Earth-fault current and screen sizing on a 10 km feeder.

In a screened 10 kV network the earth-fault current is mostly capacitive: I ≈ 3 · ω · C · U₀. With a typical per-phase capacitance of 0.3 µF/km, a 10 km feeder returns roughly 17 A of capacitive earth-fault current. The Cu wire screen (16–25 mm² on these conductor sizes) is then checked adiabatically against the protection clearing time. Tell us the earthing scheme — solid, resistance or Petersen-coil earthed — and we size the screen and state the resulting short-circuit duty in the offer.

§03 — Standards

Standards printed on the sheath and on the drum card.

IEC 60502-2GB/T 12706.2BS 6622BS 7835 (LSZH)IEC 60332-3CIEC 61034-2IEC 60754-1/2EN 50575 CPRICEA S-10634

§05 — Quality testing

What we test on every drum.

Routine tests run on every drum; sample tests on each batch; type tests on new constructions witnessed by CNAS-accredited third-party labs.

  • Conductor DC resistance at 20 °C (routine)
  • AC voltage withstand AC 21 kV / 5 min (routine)
  • Partial discharge ≤ 10 pC at 10.4 kV (1.73 U₀) (sample)
  • Insulation thickness & eccentricity (sample)
  • Metallic screen cross-section (routine)
  • Armour coverage & bedding integrity (routine)
  • Sheath thickness + spark test (routine)
  • Bending test + voltage after bending (type)
  • Impulse voltage 95 kV (type)
Routine electrical testing of medium voltage cable in the Lulian in-house laboratory
Routine electrical test · in-house lab

§06 — Packaging & delivery

Drums sized for the cable, not for the workshop.

Long rural feeders ship on the largest steel-plywood drums the route allows, keeping the joint count on the line low; bending radius is preserved from first pay-off to final termination. Wooden drums with fumigation marks for export; steel-plywood drums for heavy cross-sections. Cable ends sealed with heat-shrink caps; shipping marks per the buyer’s format.

Standard drum lengths: 500 / 1000 / 1500 / 2000 m. Lead time: 25–35 working days for stocked constructions; 40–55 working days for project-specific builds.

§07 — FAQ

Common questions on 10 kV cable procurement.

What is the U₀/U rating of 10 kV XLPE cable?

6 / 10 kV, Uₘ = 12 kV — the standard IEC class for 10 kV public distribution. The 6.35/11 kV BS designation shares the same insulation wall and test regime; the difference is marking convention, not construction.

What conductor cross-sections are available?

Three-core: 25–400 mm². Single-core: 25–630 mm². Copper or aluminium, class 2 stranded; sector-shaped conductors for large 3-core sizes.

Can the cable be direct-buried?

Yes. The armoured construction (STA) with PVC ST2 outer sheath is rated for direct burial. SWA is recommended where tensile load or rodent risk is high.

What is the partial discharge limit?

≤ 10 pC measured at 10.4 kV (1.73 U₀) per IEC 60502-2. PD is measured on every drum and documented on the routine test report.

What routine and type tests are performed?

Routine on every drum: conductor DC resistance, AC voltage withstand AC 21 kV / 5 min, sheath spark test. Sample: PD, insulation thickness, screen check. Type: bending + voltage, load cycle, impulse voltage 95 kV.

Can the cable be supplied with LSZH sheath?

Yes, for tunnel, metro, data centre and indoor substation use. Verified against IEC 61034 (smoke density) and IEC 60754 (acid gas).

What is the difference between 6/10 kV and 6.35/11 kV cable?

Both belong to the Uₘ = 12 kV class with the same 3.4 mm XLPE wall and test regime. 6/10 kV is the IEC designation used in most markets; 6.35/11 kV is the BS 6622 designation used in UK-influenced networks. We mark the drum to whichever designation your specification names.

Envíe el programa de cables. Confirmamos la construcción en 24 horas.

Share voltage class, conductor material & size, core count, armour, sheath, installation method, total length and drum preference.

RFQ por correo → sales@luliancable.comAbrir formulario de RFQ

Tensión (U₀/U)6 / 10 kV
ConductorCu / Al clase 2
Cross-section3 × 185 mm² (typical)
ArmaduraSTA / SWA / AWA
CubiertaPVC ST2 · black
NormaIEC 60502-2
IncotermFOB Qingdao · CIF [puerto]