PRODUCT FAMILY · FIRE-RESISTANT & MINERAL INSULATED · IEC 60331

Fire-Resistant & Mineral Insulated Cable

Cable built so that life-safety circuits keep working during a fire: fire pumps, smoke extraction, emergency lighting, fire-alarm power and escape-route services. Three constructions cover everything from the highest-integrity rigid cable to flexible LSZH designs.

BTTZ rigid MIBTLY flexible MIBBTRZ LSZHIEC 60331 · BS 6387Diseño patentado

§01 — Gama

Mineral insulated and fire-resistant cable types

Mineral insulated fire-resistant cable: BTTZ smooth copper sheath and BTLY corrugated sheath
BTTZ & BTLY · factory photo
QUÉ SIGNIFICA LA CLASIFICACIÓN

Resistente al fuego ≠ retardante de llama

Flame-retardant (ZR) cable resists ignition and stops flame spread, but is not expected to work during the fire. Fire-resistant (NH / MI) cable keeps the circuit alive — typically 90–180 minutes at 750–950 °C. Life-safety circuits need the second one.

Lea la comparación completa →

§02 — Normas

Qué exigir en la especificación.

ClasificaciónNormaDemuestra
Integridad de circuitoIEC 60331-21Funciona a llama de 750 °C durante ≥ 90 min
Fuego + agua + impactoBS 6387 C/W/ZSobrevive a fuego, rociado de agua e impacto mecánico
Bajo humo / libre de halógenosIEC 61034 / 60754Protege rutas de evacuación y equipos
Construcción MIGB/T 13033 · BS EN 60702-1Conformidad dimensional y eléctrica

Envíe el programa de cables. Confirmamos en 24 horas.

Comparta tipo, tamaño, núcleos, método de instalación, longitud total y puerto de destino.