Renewable energy projects: specifying cable for wind and solar collection networks

·

Overhead transmission and distribution grid infrastructure

§01 — RENEWABLE COLLECTION NETWORKS

Published 2026-09-16 · Technical analysis

A utility-scale wind or solar plant is, electrically, a medium voltage network that happens to sit inside a fence. Turbines and inverter stations step up to a collection voltage — commonly 20 kV, 33 kV or 35 kV depending on the country’s grid code — and feed a substation that connects to the transmission system. That collection layer is where most of the cable in the project is bought, and where specification errors show up as voltage drop complaints years later rather than as failures on day one.

Choosing the collection voltage class

The class is usually set by the grid code and the step-up transformer ratio, not by the cable supplier. Once it is fixed, the cable must be specified at the matching U0/U rating: 12/20 kV, 19/33 kV or the equivalent 35 kV class. On very large sites, developers sometimes subdivide the array into several collection rings, each with its own voltage-drop budget, rather than pushing one long feeder to the far corner.

Design factorWhere it appears in the projectSpecification response
Collection voltageTurbine or inverter transformer secondary, grid codeCable rated at the matching U0/U; insulation and screen sized for that class
Distance to the pooling substationLong radial strings, remote array cornersVoltage drop calculated per string; conductor upsized where the drop exceeds the budget
Solar DC and AC routingAbove-ground runs on racks and inside inverter housingsUV-stable sheath, or LSZH where the run enters an occupied enclosure
Ambient and conductor temperatureDesert and high-plateau sites, cable in full sunDerating applied for ambient temperature and solar radiation, not catalogue ampacity
Fault level at the collection busbarSubstation and string switchgearScreen cross-section and conductor short-circuit rating verified against the fault current
Soil and trenchingDirect-buried collection circuitsArmoured construction, bedding and backfill, thermal resistivity measured on the route
01

Above-ground runs

Cable fixed to racking, inside turbine towers or on cable trays needs a sheath that resists ultraviolet exposure and continuous high temperature. Where the run enters an inverter station, a control room or any occupied enclosure, low-smoke zero-halogen compounds are normally written into the specification.

02

Below-ground collection circuits

Trenched strings need mechanical protection and a rating calculated from real soil conditions. Grouping several circuits in one trench reduces the ampacity of each, and the effect grows with the number of circuits and the spacing between them.

§02 — SIZING AND LOSSES

Voltage drop, derating and the cost of a bigger conductor

Renewable collection circuits are long, and their load is intermittent but predictable at peak. Sizing on the continuous rating alone leaves two problems: voltage at the far end of the string may sit outside the inverter’s operating window during peak generation, and resistive losses accumulate across the whole array every hour the plant runs. Both are addressed by calculating voltage drop per string and then checking the result against the loss valuation in the project’s financial model. In practice this means a conductor one size larger than the thermal rating requires.

Sheath and material choices follow the installation. Armoured MV cable handles the buried collection circuits, which is the case covered by the 33 kV XLPE cable and 11 kV XLPE cable pages; the general medium and high voltage cable range sets out the conductor, screen and sheath options available across these classes. Inside inverter stations and control buildings, LSZH control cable is the usual companion to the power circuits, and mineral insulated fire resistant cable is specified where circuits must keep operating during a fire — typically emergency shutdown, fire pump and alarm circuits in the substation building.

§03 — FAQ

Questions asked in renewable cable tenders

Why is 33 kV the common choice for wind collection?

It carries more power per circuit over the long distances typical of wind layouts, which reduces the number of switchgear bays at the substation. Small sites with short runs often stay at 20 kV, where the equipment is cheaper.

Do solar collection circuits need UV-resistant sheaths?

Where the cable is fixed to racking or run in open tray, yes. Black polyethylene or a UV-stabilised compound is normally specified, and the route design should avoid continuous exposure where a buried duct is practical.

How is voltage drop budgeted across an array?

Each string is calculated from the inverter terminals to the collection busbar, at peak output, and the result is compared with the grid code and the inverter manufacturer’s operating window. The worst string, not the average, sets the conductor size.

Is armouring required for every buried collection circuit?

On most sites yes, because trench backfill and future excavation risk are unpredictable. The alternative — cable laid in duct with a warning tape and concrete cover — is used where the route is well controlled.

Next step

Send us the specification and we will check it against IEC 60502-2.

Voltage class, cores, conductor material, armour type, cross-section and destination port — that is everything we need to come back with a drawing, a datasheet and a drum plan.

More technical notes